Wallace Circulating Pump EV2-70-2C

Model: EV2-70-2C

Wallace Circulating Pump EV2-70-2C
For closed heating system hot water and for air conditioning system chilled water (supplied with unions)  

Installation & Operating Conditions:
Pump must be used only in clean water service without any solids, grit, or dirt. Pump to be installed such that the shaft is in a horizontal position. Pump must be installed in a weatherproof location with proper ventilation and easy access.  

  • Motor protection IP42 (must be installed in weatherproof location)
  • Maximum temperature for closed systems (110°C)
  • Cast iron pump not suitable for open systems and / or copper pipes
  • Minimum static head must be 2.5m or more for temperatures up to 80°C, 5m or more for temperatures up to 95°C and 18m or more for temperatures up to 110°C to avoid cavitations

 

Manufacturer: Smedegaard (Denmark)
Motor Size (P2): 0.04kW
Inlet (mm): 25 (from unions)
Power Supply: 1Ph / 230v / 50Hz
Outlet (mm): 25 (from unions)
Full Load Amps: 0.15/0.25/0.35 speeds 1/2/3
Casing Length: 130mm W/O Unions
Max Working Press: 10 bar
Casing Material: Cast Iron
Weight (Kg): 3.3 (Approx)
Speeds: Three
Dimensions (mm): 130 x 140 x 140 (Approx)