Reliance Heatguard 15 (Blue) 15mm Tempering Valve - MIX 11124

Model: MIX 11124

Reliance Heatguard 15 (Blue) 15mm Tempering Valve - MIX 11124

The RMC HeatGuard tempering valves are suitable for domestic and commercial installation on water heater systems The HeatGuard is available in 15 mm and 20 mm nominal diameters with with male compression integral union fittings.  

RMC's HeatGuard is a tempering valve that mixes hot water with cold water to deliver tempered water at a constant temperature throughout an entire house, building or system. HeatGuard is suitable for tempering the hot water supply to sanitary devices intended for personal hygiene purposes, where outlet temperature must not exceed a maximum of 50°C. HeatGuard is compatible with most storage water heaters. HeatGuard is available in 15 mm and 20 mm confi gurations.  

  • Union connections
    Valve easy to install and easy to remove for servicing of strainers
  • Performance
    More accurate control of outlet temperature – safer installations
  • Strainers upstream of check valves
    Protects valve and check valves from impurities in the water supply ™
  • Tamper-proof adjustment
    Special adjuster key eliminates chances of accidental adjustment
  • Dezincification resistant
    Meets Australian Standard for potable water supply
  • Individually tested and calibrated
    Every valve is tested to ensure higher quality and performance

Application:
RMC's HeatGuard is a tempering valve for use in hot water distribution systems. Fitting the valve at the hot water source ensures the delivery of constant temperature hot water throughout the system.

DO NOT USE on steam supplied systems.

 

Cold water supply temperature: 5° C - 30° C
Hot water supply temperature: 60° C - 99° C 
Optimum outlet temperature range: 40 C – 50° C 
Set temperature:
Must be commissioned on site to achieve desired outlet 
temperature
Accuracy of outlet temperature: ±3° C - tested to AS4032.2 between 40° C and 50° C
Minimum temperature differential:
(Between hot supply and outlet temperature)
15° C
Supply pressure, static: 1600 kPa maximum
Supply pressure imbalance, dynamic: 
(At time of commissioning)
2:1 maximum
Maximum permitted pressure variation in either supply, in order to control outlet temperature to ±3° C:
(From supply pressure at commissioning)
±10% maximum
Minimum fl ow rate: 4 litres/min
Fittings Supplied: Male BSP Thread

 

Downloads
Reliance HeatGuard Technical Specification Sheet

Plumbing Plus © 2024